Table Nepal 2

Structural Performance Factor K and other Design
Requirements for horizontal Load-Resisting Systems or
Buildings and other Structures

Item

Structural Type

Minimum Detailing
Requirements

Structural
Performance Factor K

1. (a)

 

Ductile moment-resisting frame

Must comply with the detailing for ductility requirements or is 4326 and, for steel lnnws, the additional requirements of NBC111-94

1.0

  (b)

Frame as in 1(a) with reinforced concrete shear walls

For frames : as for 1(a).
Reinforced concrete shear walls must comply with appropriate3 detailing for ductility requirements

1.01

2(a)

 

 

 

(b)

Frame as in 1(a) with either steel bracing members detailed for ductility or reinforced concrete infill panels

For frames : as for l (a).
Steel bracing members must comply with the detailing
for ductility requirements of NBC 111-94.
Reinforced concrete infill panels must comply with the detailing requirements of NBC 109-94.

1.51.2

Frame as in (a) with masonry infills

Must comply with the detailing for ductility requirements of : IS 4326

2.01.2

Diagonally-braced steel frame with ductile bracing acting in tension only

Must comply with the detailing for ductility requirements of Nepal Steel Construction Standard

2.0

Cable-stayed chimneys

Appropriate materials Standard

3.0

Structures of minimal
ductility including reinforced concrete frames not covered by 1 or 2 above, and masonry bearing wall structures.

Appropriate materials Standard

4.0

cont….